Hydrazine Monitoring in SWAS Panels
Prosoft Engineering
Technical Compliance Specialist
Start reading to track sections
Primary Keyword: SWAS Panel
Secondary Keywords: SWAS Panel Maintenance, Online SWAS Panel, SWAS Panel India
Internal Link Target: /products/swas-panels
CTA: Download our product catalogue
Introduction
Hydrazine monitoring has traditionally been associated with boiler and feedwater chemistry control in steam-generation and power-plant applications. Where hydrazine is used as an oxygen scavenger, monitoring its residual concentration can help operators maintain the desired chemical-treatment conditions and identify changes in feedwater chemistry.
An online hydrazine analyzer integrated into a properly engineered SWAS Panel provides continuous measurement without relying solely on periodic laboratory sampling.
However, reliable hydrazine measurement depends on more than the analyzer itself. Sample extraction, pressure reduction, cooling, flow control, sample-line materials, chemical conditioning, calibration, and maintenance all influence measurement performance.
This article explains the role of hydrazine monitoring in SWAS systems and the key considerations for integrating an online hydrazine analyzer into an Online SWAS Panel.
What Is Hydrazine Monitoring?
Hydrazine is a chemical that has been used in some boiler-water treatment programs primarily as an oxygen scavenger.
The objective of oxygen scavenging is to reduce dissolved oxygen and help limit corrosion in parts of the feedwater and steam-water cycle.
Where hydrazine treatment is used, monitoring can help determine whether the chemical-treatment system is operating within its intended range.
Typical monitoring locations may include:
Feedwater
Economizer inlet
Boiler feedwater systems
Deaerator-related streams
Condensate systems
Other chemistry-control points specified by the plant
The appropriate monitoring point depends on the plant chemistry program and operating conditions.
Why Monitor Hydrazine?
Hydrazine concentration can change due to:
Chemical dosing variations
Dissolved oxygen changes
Feedwater chemistry changes
Deaerator performance
Chemical-treatment-system problems
Process operating changes
Continuous measurement can provide faster information about these changes than periodic manual testing.
Hydrazine monitoring may therefore help operators:
Verify chemical dosing
Detect treatment deviations
Monitor trends
Support feedwater chemistry control
Reduce dependence on manual sampling
The required hydrazine concentration should always be established according to the plant's chemistry program and applicable operating procedures.
Important Safety Consideration
Hydrazine is a hazardous chemical. It is toxic and requires appropriate controls for handling, storage, sampling, and waste management.
Therefore, a hydrazine monitoring system should be designed with appropriate:
Chemical-handling procedures
Personal protective equipment
Sample containment
Ventilation
Waste handling
Leak protection
Safety procedures
The analyzer and SWAS system should be installed and operated according to applicable plant safety requirements and the chemical supplier's safety documentation.
Role of the SWAS Panel in Hydrazine Measurement
The SWAS Panel provides controlled sample conditions between the process stream and the online analyzer.
A simplified sample path may be:
Feedwater Sample → Isolation Valve → Pressure Reduction → Cooling → Flow Control → Hydrazine Analyzer → Drain
Depending on the application, the system may also include:
Pressure gauges
Temperature indicators
Filters
Sample flow indicators
Calibration arrangements
Chemical conditioning
Sample distribution manifolds
Drain and waste handling
The purpose of the SWAS system is to provide a representative and stable sample to the analyzer.
1. Select the Correct Sample Point
Sample-point selection is critical for hydrazine monitoring.
The sample should represent the process stream where hydrazine concentration is relevant to the plant's chemistry-control strategy.
Possible sample locations can include:
Feedwater
Deaerated feedwater
Economizer inlet
Condensate
Other feedwater-related monitoring points
Before selecting a sample point, evaluate:
Sample pressure
Sample temperature
Expected hydrazine concentration
Dissolved oxygen concentration
Sample flow
Sample chemistry
Distance from the panel
Safety and accessibility
The plant's chemistry specialist should define the appropriate monitoring point.
2. Sample Pressure Reduction
Feedwater samples can be available at elevated pressure.
A pressure-reduction arrangement may therefore be required before the sample reaches the analyzer.
Typical components include:
Isolation valve
Pressure-reducing valve
Needle valve
Pressure gauge
Back-pressure regulator where required
Pressure reduction should be controlled carefully to avoid:
Flashing
Bubble formation
Flow instability
Excessive pressure drop
Changes in sample condition
The final sample pressure should remain within the analyzer manufacturer's specified range.
3. Sample Cooling
Hydrazine analyzer systems may require the process sample to be cooled before measurement.
A sample cooler should be selected according to:
Maximum sample temperature
Normal operating temperature
Sample pressure
Sample flow
Cooling-water temperature
Analyzer inlet-temperature requirement
The cooler should provide adequate performance during the plant's maximum operating conditions.
During commissioning, operators should verify the actual sample temperature at the analyzer inlet.
4. Maintain Stable Sample Flow
Stable sample flow is essential for reliable online measurement.
A typical sample-conditioning arrangement may include:
Sample Cooler → Flow-Control Valve → Flow Indicator → Hydrazine Analyzer
The analyzer manufacturer's specified flow range should be followed.
Low flow can result in:
Slow response
Poor sample replacement
Measurement instability
Excessive flow can increase:
Sample consumption
Drain load
Pressure fluctuations
A controlled and repeatable sample flow is therefore preferred.
5. Minimize Sample Transport Time
Hydrazine chemistry can be sensitive to sample conditions and residence time.
For this reason, the sample line between the extraction point and analyzer should generally be as short as practical.
Long sample lines can result in:
Delayed response
Chemical changes
Increased residence time
Greater contamination risk
Difficulty maintaining sample conditions
The sample system should be engineered to minimize unnecessary dead volume.
6. Sample-Line Material Selection
Material selection is important in low-level water chemistry measurement.
Depending on the application, sample tubing may use materials such as:
Stainless steel
PTFE
PFA
Other compatible materials
The selection should be based on:
Sample chemistry
Temperature
Pressure
Analyzer requirements
Plant standards
The objective is to minimize contamination, chemical interaction, and adsorption effects.
7. Hydrazine Analyzer Measurement Principle
The measurement principle depends on the analyzer technology.
Online hydrazine analyzers may use chemical, electrochemical, optical, or other analytical approaches depending on the manufacturer and model.
A typical analyzer system may:
Receive a conditioned sample.
Prepare or condition the sample.
Measure the hydrazine concentration.
Apply calibration data.
Display and transmit the concentration.
Before selecting an analyzer, the exact measurement principle and sample requirements should be reviewed carefully.
8. Chemical Conditioning
Some hydrazine measurement technologies may require chemical conditioning or reagents.
Where required, the system should provide:
Reagent storage
Reagent dosing
Reagent tubing
Controlled reaction conditions
Reagent-level monitoring
Waste handling
The chemical-conditioning system should be designed as an integral part of the analyzer installation rather than added as an afterthought.
9. Calibration of the Hydrazine Analyzer
Calibration is essential for maintaining reliable hydrazine measurement.
Depending on the analyzer, calibration may include:
Zero calibration
Single-point calibration
Multi-point calibration
Standard-solution verification
Calibration standards should be prepared and handled according to the analyzer manufacturer's recommendations.
Particular attention should be given to:
Standard concentration
Standard preparation
Storage
Expiry
Contamination
Calibration frequency
Calibration records should form part of the plant's analyzer maintenance documentation.
10. Interference and Sample Chemistry
Hydrazine measurement can be affected by the chemistry of the sample and the selected measurement technology.
Potential factors may include:
Dissolved oxygen
Oxidizing chemicals
Temperature
pH
Other chemical species
Sample residence time
The analyzer should therefore be selected based on the actual water chemistry rather than solely on the required measurement range.
Where necessary, the application should be reviewed by an analytical specialist before finalizing the SWAS configuration.
11. Drainage and Waste Handling
The SWAS Panel should provide a safe drainage arrangement.
If chemical reagents are used, the waste stream may contain sample and chemical residues.
The drainage system should prevent:
Back pressure
Flooding
Cross-contamination
Uncontrolled chemical discharge
Waste should be handled according to plant environmental, safety, and chemical-waste procedures.
12. DCS and SCADA Integration
A modern Online SWAS Panel can integrate the hydrazine analyzer with the plant automation system.
Depending on the analyzer, interfaces can include:
4–20 mA
Digital outputs
RS-485
Modbus
Ethernet
Other industrial communication protocols
Typical signals include:
Hydrazine concentration
High hydrazine alarm
Low hydrazine alarm
Analyzer fault
Calibration status
Maintenance status
Communication status
During commissioning, the complete signal path should be tested from the analyzer to the DCS, PLC, SCADA, or historian.
13. Alarm Configuration
Hydrazine alarm limits should be established by the plant's chemistry team.
Possible alarm functions include:
High hydrazine
Low hydrazine
Analyzer fault
Calibration failure
Low sample flow
Reagent low
Communication failure
Alarm limits should be based on the specific treatment program, sample location, boiler chemistry, and plant operating procedures.
14. Multi-Parameter SWAS Integration
Hydrazine monitoring may be integrated with other feedwater and steam-cycle measurements.
A multi-parameter SWAS Panel India system could include:
ParameterMonitoring PurposeHydrazineOxygen-scavenger residual monitoring where applicableDissolved oxygenOxygen controlpHFeedwater chemistryConductivityGeneral water chemistryCation conductivityContamination monitoringSilicaSteam/water puritySodiumIonic contamination
The system should be designed so that each analyzer receives the sample conditions appropriate for its measurement technology.
15. Commissioning a Hydrazine Analyzer
A systematic commissioning procedure is recommended.
Step 1 – Mechanical inspection
Check:
Sample tubing
Valves
Pressure-reduction devices
Cooler
Flow-control devices
Analyzer connections
Drain system
Step 2 – Leak testing
Check all sample and utility connections.
Step 3 – Flush the sample system
Flush the sample line according to the analyzer and SWAS commissioning procedure.
Step 4 – Establish sample conditions
Verify:
Pressure
Temperature
Flow
Step 5 – Start the analyzer
Follow the manufacturer's startup instructions.
Step 6 – Check reagents or conditioning chemicals
Verify correct installation and suitability.
Step 7 – Calibrate
Perform the recommended calibration procedure.
Step 8 – Allow stabilization
Allow sufficient time for the analyzer and sample system to stabilize.
Step 9 – Test outputs
Verify:
Analog output
Digital signals
Alarms
Communication
Step 10 – Validate the result
Where appropriate, compare the online measurement against an independent laboratory or reference measurement.
SWAS Panel Maintenance for Hydrazine Monitoring
Regular SWAS Panel Maintenance should cover both the sample-conditioning equipment and analyzer.
Sample-system maintenance
Inspect:
Sample flow
Sample pressure
Sample temperature
Sample tubing
Valves
Cooler
Filters
Drainage
Leaks
Analyzer maintenance
Check:
Calibration
Sensor or measurement cell
Reagents
Reagent tubing
Pumps
Optical/electrochemical components where applicable
Diagnostic alarms
Safety maintenance
Because hydrazine is hazardous, also inspect:
Chemical connections
Reagent containers
Waste lines
Leak protection
Ventilation
Chemical labels
Safety equipment
Maintenance personnel should follow the site's approved chemical-handling procedures.
Common Hydrazine Analyzer Problems
Unstable readings
Potential causes include:
Variable sample flow
Temperature fluctuations
Air bubbles
Sample contamination
Analyzer calibration problems
Chemical-conditioning problems
Unexpectedly high hydrazine reading
Possible causes include:
Actual increase in chemical dosing
Process chemistry change
Calibration error
Sample contamination
Analyzer malfunction
The online measurement should be reviewed against process conditions and, where appropriate, a reference measurement.
Low or zero reading
Possible causes include:
No sample flow
Blocked sample line
Low hydrazine concentration
Calibration issue
Analyzer fault
Reagent/conditioning problem
Slow response
Potential causes include:
Long sample line
Low sample flow
Excessive sample volume
Sample-conditioning problems
Analyzer stabilization time
Best Practices for Hydrazine Monitoring
1. Select a representative sample point
The monitoring location should be relevant to the plant's chemistry-control strategy.
2. Keep the sample path short
Minimize transport time and dead volume.
3. Control temperature
Use a properly sized sample cooler where required.
4. Maintain stable flow
Follow the analyzer's specified sample-flow requirements.
5. Minimize contamination
Use appropriate sample-line materials and clean installation practices.
6. Maintain calibration discipline
Use suitable standards and maintain calibration records.
7. Integrate safety into the design
Hydrazine handling requires appropriate containment, waste management, and personnel protection.
8. Maintain the complete SWAS system
Troubleshooting should consider the sample-conditioning system as well as the analyzer.
Selecting a Hydrazine Analyzer for a SWAS Panel
Before selecting an analyzer, evaluate:
Selection ParameterImportanceMeasurement rangeHighDetection capabilityHighSample temperatureHighSample pressureHighSample flowHighMeasurement response timeMedium/HighMeasurement principleHighReagent requirementsMedium/HighCalibration methodHighMaintenance requirementsHighDCS/SCADA interfaceHighAlarm functionsMedium/HighSpare-parts availabilityHighLocal technical supportHighChemical safety requirementsVery HighTotal cost of ownershipHigh
For a SWAS Panel India project, availability of local technical support, spare parts, calibration assistance, and operator training should also be considered.
Hydrazine Monitoring Versus Dissolved Oxygen Monitoring
Hydrazine and dissolved oxygen provide different information about feedwater chemistry.
ParameterPrimary InformationHydrazineResidual oxygen-scavenger concentration where hydrazine treatment is usedDissolved OxygenActual dissolved oxygen concentration
Monitoring both parameters can provide a more complete picture of the effectiveness of an oxygen-control strategy where applicable.
However, the exact monitoring philosophy should be established by the plant chemistry team.
Benefits of Online Hydrazine Monitoring
An online hydrazine analyzer integrated into a SWAS system can provide:
Continuous monitoring
Faster detection of treatment changes
Reduced dependence on manual sampling
Better visibility of chemical-treatment performance
Trend monitoring
Integration with DCS/SCADA
Improved process control
Better documentation of chemistry conditions
These benefits are particularly valuable where feedwater chemistry needs close and continuous monitoring.
Hydrazine Monitoring in Modern Online SWAS Panels
A modern SWAS installation can integrate hydrazine measurement with automated sample conditioning and centralized plant monitoring.
A typical arrangement is:
Feedwater Sample
↓
Sample Isolation
↓
Pressure Reduction
↓
Sample Cooling
↓
Flow Control
↓
Hydrazine Analyzer
↓
Drain / Waste Handling
↓
DCS / SCADA / Historian
Additional analyzers can be integrated through a multi-stream sample-conditioning system.
Frequently Asked Questions
Why is hydrazine monitored in a SWAS system?
Where hydrazine is used as part of a boiler-water treatment program, monitoring its residual concentration can help operators assess chemical-treatment conditions and identify changes in the feedwater system.
Is hydrazine still used in every modern power plant?
No. Treatment chemistry varies by plant design and operating philosophy. Some facilities use alternative oxygen-control strategies. Hydrazine monitoring is therefore application-specific.
Is hydrazine hazardous?
Yes. Hydrazine requires appropriate handling, containment, personal protection, ventilation, and waste-management procedures. The applicable safety documentation and plant procedures should always be followed.
Can a hydrazine analyzer be installed on an existing SWAS Panel?
Potentially, provided the existing system can provide the required sample pressure, temperature, flow, materials compatibility, drainage, and analyzer installation conditions.
Can hydrazine and dissolved oxygen analyzers be installed together?
Yes. They can provide complementary information about oxygen-control chemistry where hydrazine treatment is used.
How often should a hydrazine analyzer be calibrated?
The appropriate calibration frequency depends on analyzer technology, operating conditions, required accuracy, and manufacturer recommendations.
What causes unstable hydrazine measurements?
Common causes include unstable sample flow, temperature changes, contamination, air bubbles, calibration problems, chemical-conditioning problems, and analyzer faults.
Conclusion
Hydrazine monitoring can provide valuable information for steam-cycle and feedwater chemistry control where hydrazine is part of the plant's treatment program.
A properly engineered SWAS Panel ensures that the online analyzer receives a representative sample under controlled pressure, temperature, and flow conditions. Sample-line design, material selection, calibration, chemical conditioning, drainage, safety, and preventive maintenance all contribute to reliable measurement.
For long-term performance, the hydrazine analyzer should be treated as part of the complete sample-conditioning and water-chemistry monitoring system rather than as an isolated instrument.