General5 Min Read · Published 2026-09-15

Feedwater Monitoring via SWAS

P

Prosoft Engineering

Technical Compliance Specialist

"Feedwater chemistry can be affected by condensate contamination, make-up water quality, chemical dosing, deaerator performance, corrosion products and other process conditions. If contaminants enter the boiler through the feedwater system, they can become concentrated or transported through the steam-water cycle."
Reading progress0%

Start reading to track sections

Primary Keyword: SWAS Panel
Secondary Keywords: SWAS Panel Maintenance, Online SWAS Panel, SWAS Panel India
Internal Link: /products/swas-panels
CTA: Talk to our application specialist

Introduction

Feedwater is one of the most important streams in a boiler and steam-water cycle. It carries treated water back toward the boiler or steam-generating equipment, making its chemical quality critical for controlling corrosion, deposition and contamination.

Feedwater chemistry can be affected by condensate contamination, make-up water quality, chemical dosing, deaerator performance, corrosion products and other process conditions. If contaminants enter the boiler through the feedwater system, they can become concentrated or transported through the steam-water cycle.

A properly engineered SWAS Panel (Steam and Water Analysis System) enables continuous monitoring of important feedwater chemistry parameters.

An Online SWAS Panel can integrate measurements such as conductivity, cation conductivity, pH, dissolved oxygen, sodium, silica and other parameters according to the plant's chemistry-control requirements.

For power plants, HRSG systems, captive power plants, cogeneration facilities and industrial boilers, reliable feedwater monitoring provides an important layer of protection for the complete steam-water cycle.


What Is Feedwater?

Feedwater is water supplied to a boiler, HRSG or steam-generating system for conversion into steam.

Depending on the plant configuration, feedwater may originate from:

  • Condensate

  • Condensate polishing systems

  • Demineralized water

  • Make-up water

  • Deaerator outlet

  • Feedwater treatment systems

Before entering the boiler, feedwater is normally treated and conditioned to control dissolved gases, ionic impurities and other contaminants.

The exact treatment and chemistry-control approach depends on:

  • Boiler design

  • Operating pressure

  • Materials

  • Cycle configuration

  • Water-treatment system

  • Chemistry program

  • OEM requirements


Why Is Feedwater Monitoring Important?

Feedwater is continuously introduced into the steam-generating system.

Therefore, poor feedwater quality can influence the entire cycle.

Potential consequences of inadequate feedwater chemistry include:

  • Corrosion

  • Deposition

  • Scaling

  • Boiler-tube damage

  • Steam contamination

  • Turbine deposition

  • Reduced heat-transfer efficiency

  • Increased chemical consumption

  • Reduced equipment reliability

Continuous monitoring helps operators identify changes early.


Role of a SWAS Panel in Feedwater Monitoring

A SWAS Panel provides the controlled sample-conditioning and analytical arrangement required to measure feedwater.

A typical sample path may be:

Feedwater Sample Point → Isolation Valve → Pressure Control → Sample Cooler → Temperature Measurement → Filtration → Flow Control → Analyzer → Drain/Return

Depending on the application, the system can include multiple analyzers.

The SWAS design should consider:

  • Feedwater pressure

  • Feedwater temperature

  • Sample flow

  • Required analytical parameters

  • Sample-line length

  • Cooling-water availability

  • Analyzer requirements

  • Plant chemistry philosophy


Typical Feedwater Sampling Points

Feedwater systems contain several potential monitoring locations.

1. Deaerator Outlet

Monitoring downstream of the deaerator can provide information about the chemistry of water entering the feedwater system.

Dissolved oxygen monitoring can be particularly relevant where required by the plant chemistry program.

2. Feedwater Pump Discharge

The feedwater pump discharge may provide a useful location for monitoring water quality before the water reaches the boiler or HRSG.

3. Economizer Inlet

In some applications, monitoring near the economizer inlet can provide information about the chemistry entering the boiler heat-recovery section.

4. Boiler Feedwater

A dedicated boiler feedwater sample point can be incorporated into the SWAS system according to the plant's chemistry-monitoring philosophy.

5. HRSG Feedwater

Combined-cycle plants may monitor feedwater associated with the HP, IP or LP circuits.

The actual sampling location should be selected based on the plant P&ID, representative sampling requirements and analyzer specifications.


Feedwater Parameters Commonly Monitored

The exact parameters depend on the plant design and chemistry program.

Typical measurements may include:

ParameterTypical PurposeConductivityGeneral ionic contamination monitoringCation ConductivitySensitive monitoring of certain ionic contaminantsDegassed Cation ConductivityHelps evaluate dissolved-gas contributionpHFeedwater chemistry controlDissolved OxygenCorrosion-control monitoringSodiumSensitive contamination monitoringSilicaMonitoring where silica transport/contamination is relevantTemperatureSample-condition monitoring

Other parameters can be added where required.


Conductivity Monitoring in Feedwater

Conductivity is a basic but valuable measurement for feedwater chemistry.

Changes in conductivity can indicate changes in ionic contamination.

Possible sources include:

  • Condensate contamination

  • Make-up water contamination

  • Chemical dosing

  • Treatment-system performance

  • Process leakage

  • Sample contamination

Continuous conductivity monitoring provides trend information and can help operators identify changes before they become significant.


Cation Conductivity Monitoring

Cation conductivity provides additional sensitivity to certain ionic contaminants.

The sample passes through a cation exchanger before reaching the conductivity cell.

A typical arrangement is:

Feedwater → Cooler → Flow Control → Cation Exchanger → Conductivity Cell

The condition of the cation resin is important.

If the resin becomes exhausted or contaminated, the measurement may no longer represent the intended analytical condition.

Cation resin should therefore be inspected and maintained according to the system design and manufacturer's recommendations.


Degassed Cation Conductivity

Dissolved carbon dioxide can contribute to conductivity after cation exchange.

A degassed cation conductivity system removes or reduces the influence of dissolved gases before the final conductivity measurement.

Comparing cation conductivity with degassed cation conductivity can provide additional diagnostic information.

However, plant chemistry conditions must be considered when interpreting the results.


pH Monitoring of Feedwater

pH control is an important component of many feedwater chemistry programs.

An online pH analyzer can provide continuous measurement and help identify changes in feedwater chemistry.

Reliable pH measurement requires attention to:

  • Sensor selection

  • Reference electrode condition

  • Temperature compensation

  • Sample flow

  • Calibration

  • Sample cleanliness

High-purity water can be challenging for pH measurement, so the analyzer and sample system should be specifically selected for the application.


Dissolved Oxygen Monitoring

Dissolved oxygen can play an important role in corrosion control.

A deaerator is commonly used in many boiler systems to reduce dissolved gases before feedwater enters the boiler.

Online dissolved oxygen monitoring can help evaluate the effectiveness of the chemistry-control system where DO measurement is part of the plant's monitoring strategy.

DO measurement is sensitive to air ingress.

Therefore, the sample system should minimize:

  • Leaks

  • Loose fittings

  • Air bubbles

  • Unnecessary dead legs

  • Excessive sample-line residence time


Sodium Monitoring

Sodium can be used as a sensitive indicator of certain contamination events.

Possible sources include:

  • Condenser leakage

  • Cooling-water ingress

  • Make-up water contamination

  • Treatment-system problems

  • Process contamination

Continuous sodium monitoring can provide early warning where low-level contamination detection is important.

Because sodium analyzers can be sensitive to sample contamination, sample-system cleanliness is essential.


Silica Monitoring

Silica can be included in feedwater monitoring where required by the plant chemistry program.

The importance of silica increases in applications where silica transport with steam and downstream deposition are concerns.

Online silica analysis can help operators monitor changes and investigate abnormal chemistry conditions.

Silica analyzer performance depends on:

  • Sample cleanliness

  • Sample flow

  • Temperature

  • Reagent condition

  • Calibration

  • Drainage


Sample Conditioning for Feedwater Monitoring

A feedwater sample may still require conditioning before it reaches an analyzer.

A typical conditioning arrangement can include:

  1. Sample isolation valve

  2. Pressure-reduction/control device

  3. Sample cooler

  4. Temperature sensor

  5. Filter

  6. Flowmeter

  7. Flow-control valve

  8. Analyzer manifold

  9. Calibration connection

  10. Drain or sample return

The objective is to provide a stable, representative and analyzer-compatible sample.


Pressure Reduction

Feedwater pressure can be high, particularly near the boiler feed pump discharge.

Analytical instruments generally require much lower and controlled pressure.

A pressure-control system may therefore be installed upstream of the analyzer.

The design should consider:

  • Maximum pressure

  • Normal pressure

  • Temperature

  • Flow

  • Pressure drop

  • Valve characteristics

  • Flashing risk

  • Analyzer requirements

There is no universal SWAS pressure setting.

The correct arrangement must be engineered according to actual plant conditions and analyzer specifications.


Feedwater Sample Cooling

Feedwater temperature may be too high for direct connection to many analytical instruments.

A sample cooler can reduce the temperature to the appropriate analyzer operating range.

Cooling performance depends on:

  • Sample temperature

  • Sample flow

  • Cooling-water temperature

  • Cooling-water flow

  • Heat-transfer area

  • Cooler material

  • Fouling

A simplified heat balance is:

Q = m × Cp × ΔT

Actual cooler sizing should be based on the complete process conditions and appropriate engineering calculations.


Sample Flow Control

Stable sample flow is important for reliable measurements.

The system may use:

  • Flowmeters

  • Rotameters

  • Needle valves

  • Flow-control valves

  • Pressure regulators

The required flow must be determined from the individual analyzer manufacturer's specification and the complete sample-conditioning design.

Too little flow can cause excessive transport delay and unstable measurements.

Excessive flow can increase water consumption and may affect the performance of the cooling and conditioning system.


Sample-Line Design for Feedwater

The sample line should be designed to provide a representative sample while minimizing delay and contamination.

Good design practices include:

  • Keep lines as short as practical

  • Minimize unnecessary bends

  • Avoid dead legs

  • Use appropriate materials

  • Prevent air ingress

  • Provide adequate drainage

  • Maintain stable flow

  • Provide accessibility for maintenance

Sample transport time can be estimated as:

Transport Time = Sample-Line Volume ÷ Sample Flow Rate

This becomes particularly important when rapid detection of chemistry changes is required.


Material of Construction

Material selection should be based on:

  • Feedwater chemistry

  • Pressure

  • Temperature

  • Corrosion resistance

  • Cleanliness

  • Analyzer requirements

Common materials may include:

  • SS 316/316L

  • SS 304/304L

  • PTFE

  • PFA

  • PVDF

For low-level measurements, the cleanliness and compatibility of wetted components can have a significant influence on measurement reliability.


Feedwater Monitoring in Thermal Power Plants

In thermal power plants, feedwater chemistry is closely connected to boiler and steam chemistry.

A SWAS system may monitor:

  • Condensate

  • Feedwater

  • Boiler water

  • Main steam

  • Reheat steam

  • Make-up water

Typical feedwater measurements may include:

  • Conductivity

  • Cation conductivity

  • pH

  • Dissolved oxygen

  • Sodium

  • Silica

The exact combination depends on the plant's chemistry program.


Feedwater Monitoring in Combined-Cycle Plants

Combined-cycle plants use HRSG systems to recover heat from gas-turbine exhaust and generate steam.

Feedwater monitoring can be associated with:

  • HP feedwater

  • IP feedwater

  • LP feedwater

  • Deaerator system

  • Condensate system

  • HRSG circuits

An integrated Online SWAS Panel can provide continuous measurements across multiple sample points.


Feedwater Monitoring in Captive Power Plants

Captive power plants in industries such as:

  • Steel

  • Cement

  • Sugar

  • Paper

  • Chemicals

  • Textiles

often operate their own boilers and steam systems.

Reliable feedwater monitoring can help support:

  • Boiler reliability

  • Chemistry control

  • Reduced corrosion risk

  • Reduced contamination

  • Improved operational stability

A suitably configured SWAS Panel India solution can be designed around the specific boiler and feedwater system.


Feedwater Monitoring in Industrial Boilers

Industrial boilers may have different chemistry requirements from large utility power plants.

The monitoring system should therefore be scaled according to:

  • Boiler pressure

  • Boiler capacity

  • Water-treatment system

  • Feedwater chemistry

  • Steam use

  • Material selection

  • Process requirements

A smaller industrial boiler may require fewer analytical parameters, while a high-pressure utility or HRSG system may require a broader chemistry-monitoring package.


PLC, HMI and DCS/SCADA Integration

A modern SWAS Panel can transmit feedwater chemistry information to the plant automation system.

Typical signals include:

  • Analyzer measurements

  • Sample temperature

  • Sample flow

  • Sample pressure

  • Analyzer status

  • Calibration status

  • Common fault

  • High/low alarms

Communication can be implemented using suitable interfaces such as:

  • 4–20 mA

  • Digital signals

  • Modbus RTU

  • Modbus TCP

  • Ethernet

  • Other plant-approved protocols

The final architecture should be established during system engineering.


Feedwater Chemistry Alarm Management

Alarm configuration should cover both chemistry and sample-system conditions.

Chemistry alarms

Potential alarms include:

  • High conductivity

  • High cation conductivity

  • High sodium

  • High silica

  • High/low pH

  • High dissolved oxygen

Sample-system alarms

Examples include:

  • Low sample flow

  • High sample temperature

  • High sample pressure

  • Low cooling-water flow

  • Filter blockage

Analyzer alarms

Examples include:

  • Calibration failure

  • Sensor failure

  • Reagent low

  • Analyzer fault

  • Communication failure

Alarm limits should be established according to the plant chemistry program and applicable equipment requirements.


SWAS Panel Maintenance for Feedwater Monitoring

Reliable feedwater monitoring requires systematic SWAS Panel Maintenance.

Daily or Routine Checks

Operators can check:

  • Analyzer readings

  • Sample flow

  • Sample temperature

  • Cooling-water flow

  • Leakage

  • Drainage

  • Alarm status

Periodic Checks

Maintenance can include:

  • Filter inspection

  • Sensor inspection

  • Calibration

  • Valve inspection

  • Sample tubing inspection

  • Cooler inspection

  • Cation resin inspection

  • Reagent replacement where applicable

Planned Maintenance

Depending on the equipment and manufacturer's recommendations:

  • Detailed analyzer servicing

  • Sensor replacement

  • Calibration verification

  • Sample cooler inspection

  • Valve maintenance

  • Electrical inspection

  • PLC/HMI checks

  • DCS communication verification

Maintenance intervals should be established according to actual operating conditions and manufacturer recommendations.


Common Feedwater SWAS Problems

High Conductivity

Possible causes include:

  • Actual contamination

  • Condensate contamination

  • Make-up water contamination

  • Chemical dosing

  • Treatment-system problems

  • Sample-system contamination


High Cation Conductivity

Investigate:

  • Ionic contamination

  • Condenser-related contamination

  • Cation resin condition

  • Sample-system cleanliness

  • Analyzer condition


High Dissolved Oxygen

Possible causes include:

  • Deaerator performance issues

  • Air ingress

  • Sample-line leakage

  • Poor sample conditioning

  • Sensor/calibration problems


High Sodium

Investigate:

  • Condenser leakage

  • Cooling-water ingress

  • Make-up water

  • Process contamination

  • Sample-system contamination

  • Analyzer/reagent condition


Unstable Readings

Check the complete sample path:

  • Sample pressure

  • Sample flow

  • Sample temperature

  • Air bubbles

  • Filter

  • Sensor

  • Calibration

  • Analyzer

  • Electrical connections


Feedwater SWAS Troubleshooting Sequence

A systematic approach can reduce unnecessary analyzer replacement.

Use the following sequence:

Process → Sample Point → Pressure → Cooling → Flow → Filtration → Sensor → Analyzer → Signal → DCS/SCADA

This separates process chemistry problems from sample-conditioning and instrumentation problems.


Dedicated vs Multiplexed Feedwater Monitoring

Dedicated Monitoring

Dedicated analyzers can continuously monitor individual sample streams.

Advantages

  • Continuous measurement

  • Fast response

  • Simple interpretation

  • No switching delay

  • Suitable for critical parameters

Multiplexed Monitoring

A multiplexed SWAS system can sequentially analyze several sample streams.

Advantages

  • Lower analyzer count

  • Centralized system

  • Potential capital-cost reduction

  • Useful where continuous measurement at every point is not required

However, multiplexed systems require careful management of:

  • Switching sequence

  • Flushing

  • Cross-contamination

  • Transport delay

  • Valve reliability

  • Dead volume


Relationship Between Feedwater and Condensate Monitoring

Feedwater and condensate monitoring should be viewed as interconnected parts of the steam-water cycle.

A simplified cycle is:

Boiler → Steam → Turbine/Process → Condenser → Condensate → Feedwater → Boiler

If condensate becomes contaminated, the contamination can potentially propagate into the feedwater system.

Monitoring both locations can therefore help identify where a chemistry problem may have originated.


Feedwater Monitoring and Deaerator Performance

The deaerator plays an important role in many boiler systems by reducing dissolved gases from feedwater.

Where dissolved oxygen monitoring is included, comparing measurements around the deaerator can provide useful information about system performance.

Other factors should also be considered, including:

  • Operating temperature

  • Pressure

  • Venting

  • Sample-system integrity

  • Oxygen scavenging/chemical treatment where applicable

The exact chemistry-control strategy varies by plant.


Feedwater SWAS Selection Checklist

Before selecting a system, collect:

Process Information

  • Feedwater source

  • Pressure

  • Temperature

  • Flow

  • Normal operating conditions

  • Maximum operating conditions

  • Sample-point location

Analytical Requirements

  • Conductivity

  • Cation conductivity

  • Degassed cation conductivity

  • pH

  • Dissolved oxygen

  • Sodium

  • Silica

  • Other required parameters

Sample Conditioning

  • Pressure reduction

  • Cooling

  • Filtration

  • Flow control

  • Drain/return

  • Calibration arrangement

Automation

  • PLC

  • HMI

  • DCS/SCADA

  • Communication protocol

  • Alarm requirements

  • Data logging

Mechanical Requirements

  • Panel material

  • Tubing material

  • Valve material

  • Cooler material

  • Pressure rating

  • Installation environment


Best Practices for Feedwater Monitoring via SWAS

For reliable operation:

  1. Select a representative feedwater sample point.

  2. Keep sample lines as short as practical.

  3. Minimize dead legs and unnecessary fittings.

  4. Use appropriate pressure reduction.

  5. Design the cooler for actual process conditions.

  6. Maintain stable sample flow.

  7. Prevent air ingress.

  8. Use suitable wetted materials.

  9. Maintain filters and cation exchangers.

  10. Calibrate analyzers according to manufacturer requirements.

  11. Integrate alarms with the plant control system.

  12. Compare online results with laboratory measurements where appropriate.

  13. Maintain historical trends.

  14. Keep critical spare parts available.

  15. Follow a documented SWAS Panel Maintenance program.


Benefits of an Online SWAS Panel for Feedwater

A properly designed Online SWAS Panel can provide:

  • Continuous feedwater chemistry monitoring

  • Early contamination detection

  • Better boiler chemistry control

  • Improved corrosion-risk management

  • Reduced dependence on manual sampling

  • Continuous trend information

  • Automated alarms

  • DCS/SCADA integration

  • Faster troubleshooting

  • Improved maintenance planning

  • Better steam-cycle reliability


Why Choose Prosoft Automation for Feedwater SWAS?

Prosoft Automation provides application-oriented SWAS solutions for steam and water chemistry monitoring.

Our approach considers the complete measurement chain:

Sample Extraction → Pressure Reduction → Cooling → Conditioning → Flow Control → Online Analysis → PLC/HMI → DCS/SCADA

This approach is important because the performance of a water chemistry analyzer depends heavily on the quality and stability of the sample supplied to it.

Prosoft solutions can be configured for:

  • Feedwater monitoring

  • Condensate monitoring

  • Boiler-water monitoring

  • Saturated-steam monitoring

  • Superheated-steam monitoring

  • HRSG applications

  • Thermal power plants

  • Captive power plants

  • Cogeneration plants

  • Industrial boilers

  • Process industries


Frequently Asked Questions

What is feedwater monitoring via SWAS?

Feedwater monitoring via SWAS is the continuous analysis of boiler or HRSG feedwater to monitor important chemical parameters and identify contamination or chemistry changes.

Which parameters are commonly monitored in feedwater?

Conductivity, cation conductivity, pH and dissolved oxygen are commonly considered. Sodium, silica and degassed cation conductivity may also be included depending on the plant chemistry program.

Why is dissolved oxygen monitored in feedwater?

Dissolved oxygen can contribute to corrosion mechanisms. Where DO monitoring is part of the plant chemistry strategy, online measurement can help evaluate and control oxygen levels.

Why is conductivity important in feedwater?

Conductivity provides an indication of dissolved ionic contamination and can help identify changes in feedwater quality.

Can sodium be measured continuously in feedwater?

Yes. An online sodium analyzer can be incorporated into a SWAS system where sensitive contamination monitoring is required.

Is a sample cooler necessary for feedwater monitoring?

It depends on the actual feedwater temperature and the analyzer's allowable sample-temperature range. Where the sample is too hot, a properly designed sample cooler is required.

How often should a feedwater SWAS system be maintained?

Maintenance frequency depends on the analyzer technology, sample quality, plant conditions and manufacturer recommendations. Routine inspection, calibration, sensor checks, filter maintenance and sample-system inspection are important.

Can a feedwater SWAS Panel be connected to DCS?

Yes. A suitably engineered SWAS Panel can transmit analytical values, alarms and system status to the plant DCS/SCADA system.

What causes unstable feedwater analyzer readings?

Potential causes include fluctuating sample flow, temperature changes, air bubbles, sample contamination, sensor condition, calibration problems and analyzer faults. The complete sample path should be checked before replacing the analyzer.

What information is required to design a feedwater SWAS Panel?

Important information includes sample location, pressure, temperature, flow, required analytical parameters, sample-line length, cooling-water availability, drainage/return arrangement, automation requirements and analyzer specifications.


Conclusion

Feedwater is a critical part of every boiler and steam-water cycle. Maintaining its chemical quality helps control contamination and supports the reliable operation of boilers, HRSGs, turbines, condensers and associated equipment.

A properly engineered SWAS Panel provides the sampling, pressure control, cooling, filtration, flow control and online analysis required for continuous feedwater chemistry monitoring.

Conductivity, cation conductivity, pH, dissolved oxygen, sodium, silica and other parameters can be selected according to the plant's chemistry-control requirements.

The reliability of an Online SWAS Panel depends on the complete sample-conditioning system as well as the analyzer. Representative sampling, suitable sample-line design, stable flow and temperature, appropriate materials, proper calibration and planned SWAS Panel Maintenance are essential.

Feedwater monitoring should therefore be considered together with condensate, boiler-water and steam monitoring as part of an integrated steam and water chemistry strategy.

Prosoft Automation can support application-specific SWAS Panel solutions for feedwater, condensate, boiler water and steam monitoring in power generation and industrial process applications.

Talk to Our Application Specialist

Share your feedwater sample point, pressure, temperature, required parameters and plant application with Prosoft Automation.

Our application team can help evaluate the sampling arrangement and recommend a suitable SWAS configuration for your requirements.

Talk to our application specialist for a free site-application consultation.